title: Check status of APC Symmetra USV agents: snmp author: Mathias Kettner <mk@mathias-kettner.de> license: GPL distribution: check_mk description: This check monitors eight aspects of an APC Symmetra USV: {(1)} the battery status, {(2)} the output status, {(3)} the battery capacity, {(4)} the battery temperature, {(5)} the battery current, {(6)} the output voltage and {(7)} the output current, {(8)} the remaing run time. The output current and remaining run time are not checked against a level but just being displayed. examples: # Set the critical levels for all APC checks to: # - battery capacity at 90% or lower # - battery temperature to 38C or higher # - battery current to 10A or higher # - output voltage to 225V or lower apc_default_levels = (90, 38, 10, 225) perfdata: This check outputs five performance values: the battery capacity, the battery temperature, the battery current, the output voltage and the output current. inventory: Supported. [parameters] crit_capacity (int): The battery capacity in percent at and below which a critical state is be triggered crit_batt_temp (int): The critical temperature of the battery crit_batt_curr (int): The critical battery current in Ampere crit_voltage (int): The output voltage at and below which a critical state is triggered. [configuration] apc_default_levels (int, int, int, int): The default levels to be used for inventorized checks. This variable is preset to {(95, 40, 1, 220)}