<!doctype html public "-//w3c//dtd html 4.0 transitional//en"> <html> <head> <meta http-equiv="Content-Type" content="text/html; charset=iso-8859-1"> <meta name="Author" content="Riccardo Facchetti"> <meta name="GENERATOR" content="Mozilla/4.74 [en] (X11; U; Linux 2.4.3 i586) [Netscape]"> </head> <body text="#000000" bgcolor="#FFFFFF" link="#0000EF" vlink="#51188E" alink="#FF0000"> <h2> Talk directly to a smart UPS with minicom</h2> <p><br>To talk with your UPS with minicom, APCUPSD must not run. Therefore kill the APCUPSD before anything else. To connect to the UPS use minicom as root with the following settings. <br> <h3> Modem and dialing</h3> <p><br>A - Init string ......... Y\0^M <br>B - Reset string ........ Y^M <br>C - Dialing prefix #1.... Y\0 <br>D - Dialing suffix #1.... ^M <br>E - Dialing prefix #2.... ATDP <br>F - Dialing suffix #2.... ^M <br>G - Dialing prefix #3.... ATX1DT <br>H - Dialing suffix #3.... ;X4D^M <br>I - Connect string ...... CONNECT <br>J - No connect strings .. NO CARRIER BUSY <br> NO DIALTONE VOICE <br>K - Hang-up string ...... R\0^M <br>L - Dial cancel string .. ^M <br>M - Dial time ........... 45 P - Auto baud detect .... Yes <br>N - Delay before redial . 5 Q - Drop DTR to hangup .. No <br>O - Number of tries ..... 10 R - Modem has DCD line .. No <br> <h3> Serial port setup</h3> <p><br>A - Serial Device : /dev/ttyS3 <br>B - Lockfile Location : /var/lock <br>C - Callin Program : <br>D - Callout Program : <br>E - Baud/Par/Bits : 2400 8N1 <br>F - Hardware Flow Control : No <br>G - Software Flow Control : No <br> <p>The output of a SmartUPS is: <p>a 3.!$%+?=#|.^A+-789>@ABCDEFGKLMNOPQRSUVWXYZ'abcefgjklmnopqrsuxyz~^? <br>b 52.9.D <br>c UPS_IDEN <br>d NA <br>e 00 <br>f 079.0 <br>g 024 <br>h NA <br>i NA <br>j 0037: <br>k 0 <br>l 103 <br>m 02/18/95 <br>n S95025484481 <br>o 115 <br>p 020 <br>q 02 <br>r 000 <br>s H <br>t NA <br>u 132 <br>v NA <br>w NA <br>x 02/18/95 <br>y (C) APCC <br>z CLEAR <br>A OK <br>B 27.74 <br>C 033.3 <br>D NO <br>E 336 <br>F 60.00 <br>G S <br>H NA <br>I NA <br>J NA <br>K <br>L 126.7 <br>M 128.0 <br>N 126.1 <br>O 126.7 <br>P 023.4 <br>Q 08 <br>S NA <br>T NA <br>U OK <br>!$ <br>V GWD <br>W OK <br>X OK <br>Y SM <br>` NA <br>1 NA <br>2 NA <br>3 NA <br>4 28 <br>5 F2 <br>6 FA <br>7 00 <br>8 00 <br>9 FF <br>0 82 <br>- NO <br>= NA <br>\ NA <br>| NA <br>+ NO <br>_ NA <br>) NA <br>( NA <br>* NA <br>& NA <br>^ NA <br>% NA <br>$ NA <br># NA <br>! NA <br>` NA <br>~ 00 <br>^a SMART-UPS 700 RM <br> </body> </html>