        <TITLE>APC UPS management under Linux</TITLE>
        <META NAME="DESCRIPTION" CONTENT="apcupsd a Linux daemon for controlling APCC UPSes">
        <META NAME="KEYWORDS" CONTENT="apcupsd, UPS, APCC, Power">
   <meta name="Author" content="Kern Sibbald">
        <!-- Background white, links blue (unvisited), navy (visited), red (active) -->
                <link rel=stylesheet href="apcupsd-styles.css" type="text/css">
</HEAD>
<BODY TEXT="#000000" LINK="#0000ff" VLINK="#000080" BGCOLOR="#ffffff">
<P ALIGN=CENTER><IMG SRC="apcupsd.gif" NAME="Graphic1" ALT="[APCUPSD DOCUMENTATION]" ALIGN=BOTTOM WIDTH=584 HEIGHT=64 BORDER=0>
</P>
<H3 ALIGN=CENTER>Apcupsd Linux UPS daemon version 3.8.3 
</H3>
<H1 ALIGN=CENTER>apcupsd a program for controlling APC UPSes</H1>
<H2>SYNOPSIS</H2>
<P><B>/sbin/apcupsd</B> <BR><B>/etc/apcupsd/apccontrol</B>
<BR><B>/etc/apcupsd/apcupsd.conf</B> <BR><B>/sbin/apcaccess</B>
<BR><B>/sbin/apcnisd</B> 
</P>
<H2>DESCRIPTION</H2>
<P><B>Apcupsd </B>can be used for controlling APC UPSes.
During a power failure, <B>apcupsd</B> will inform the users about
the power failure and that a shutdown may occur. If power is not
restored, a system shutdown will follow when the battery is exhausted,
a timeout (seconds) expires, or runtime expires based on internal APC
calculations determined by power consumption rates. If the power is
restored before one of the above shutdown conditions is met, <B>apcupsd</B>
will inform users about this fact. 
</P>
<p><b>Apcupsd</b> runs on Linux systems, many Unix systems (Solaris,
FreeBSD, OpenBSD, Alpha, ...) as well as on Windows systems
(Win95/98/Me/NT/2000).</p>
<P><B>Apcupsd</B> performs the shutdown by calling
<B>/etc/apcupsd/apccontrol</B>, which is a shell script.
Consequently, no changes to /etc/inittab are necessary. There is no
communication between <B>apcupsd</B> and init(1) process. During
installation, the system halt script was modified so that at the end
of the shutdown process during a power failure, <B>apcupsd</B> will
be re-executed in order to power off the UPS. This step is not
mandatory, but is good practice as it avoids the possibility of your
system being prematurely restarted if the power returns for a short
period. It also permits your computer to be automatically rebooted
when the power is restored providing you have configured your computer
BIOS appropriately.
</P>
<P>The <B>apcupsd</B> daemon now supports two networking modes that
function independently, but if desired at the same time. 
</P>
<P>Most users will probably enable the first network mode, which
permits <B>apcupsd</B> to serve <A HREF="status.html">STATUS</A> and
<A HREF="events.html">EVENTS</A> information to clients over the
network. 
</P>
<P>The second networking mode is for multiple networked machines that
are powered by the same UPS. In this mode, one machine is configured
as a master with the UPS attached to the serial port. The other
machines (maximum 20) powered by the same UPS are configured as
slaves. The master has a network connection with the slaves and sends
them information about the UPS status. Please see the <A HREF="configure.html#UPS_Sharing">UPS
Sharing section</A> of this document for more details.</P>

<P>RedHat and SuSE. versions of Linux have direct install support, as does
Solaris.
All other flavors of Linux and Unix machines
may need some fussing with to get the
install correct. 
</P>
<h2>SUPPORTED MODELS</h2>
Please see the <A HREF="configure.html#ModelsSupported">Configuration section</A> of this document for more details.</P>
<H2>OPTIONS</H2>
<DL>
        <DT>-c --configure 
        </DT><DD>
        Attempts to configure the UPS EPROM to the values specified in the
        configuration file <B>/etc/apcupsd/apcupsd.conf</B>. 
        </DD><DT>
        -d --debug &lt;level&gt; 
        </DT><DD>
        Turns on debugging output for a NETSLAVE or a NETMASTER. 
        </DD><DT>
        -f --config-file &lt;file&gt; 
        </DT><DD>
        Specifies the location of the configuration file. The default is:
        <B>/etc/apcupsd/apcupsd.conf</B> 
        </DD><DT>
        -k --killpower 
        </DT><DD>
        Attempt to turn the UPS off. This option is normally only used by
        the daemon itself to shut the UPS off after a system shutdown has
        completed. Note, if the killpower is done by a netmaster, it will
                sleep for 30 seconds before issuing the power kill request to the
                UPS to allow the slaves to properly shutdown.
        </DD><DT>
        -n --rename-ups 
        </DT><DD>
        Attempts to change the UPS name stored in the UPS EPROM to that
        specified in your <B>/etc/apcupsd/apcupsd.conf</B> file. </DD>
     <dt>-p, --kill-on-powerfail</dt> 
        <dd>If this option is specified and a power failure occurs, immediately
            after <b>apcupsd</b> issues the system shutdown request, it will
            instruct the UPS to shut off the mains power. This option can be
            useful if your system does not let <b>apcupsd</b> regain control
            at the end of the shutdown procedure to shut off the mains power.
            However, if you use this option, you must insure that your UPS
            has a sufficiently long power off grace period to permit your
            computer to fully shutdown.</dd>
     <DT>-t, --term-on-powerfail
                </dt><dd>
                This option tells <b>apcupsd</b> to exit immediately when it issues
                the system shutdown command (i.e. calls <b>apccontrol</b>). This 
                behavior can be useful for those systems where it is not possible
                to insert <b>apcupsd</b> commands in the termination script in order
                to do the killpower. Without this option, <b>apcupsd</b> will wait 
                for the <b>SIGTERM</b> signal from the system shutdown before exiting.
                </dd>
      <dt> -u --update-battery-date 
        </DT><DD>
        Attempts to update the battery date stored in the UPS EPROM.
        Normally done after a battery replacement. 
        </DD><DT>
        -V --version 
        </DT><DD>
        Prints the <B>apcupsd</B> version number and the usage. 
        </DD><DT>
        -? --help 
        </DT><DD STYLE="margin-bottom: 0.2in">
        Prints a brief <B>apcupsd</B> help screen. 
        </DD></DL>
<H2>
FILES</H2>
<DL>
        <DT>/etc/apcupsd/apcupsd.conf - configuration file. 
        </DT><DT>
        /etc/apcupsd/apcupsd.status - STATUS file 
        </DT><DT>
        /etc/apcupsd/apcupsd.events 
        </DT><DD STYLE="margin-bottom: 0.2in">
        where up to the last 50 events are stored for the network
        information server. 
        </DD></DL>
<H2>
SEE ALSO</H2>
<P><B>apcnisd</B>(8) 
</P>
For credits, please see the <a href="thanks.html">Thanks Chapter</a> of
this manual.